Notes:
12/3/2025 10:16:20 AM
-( 63) NAPOLEON VTAC UNITS – ELECTRIC HEAT, 12-SEER AIR CONDITIONER.
-JOIST DUCTING WITH FIRE DAMPERS AND SOFFIT DUCTING FOR TOP FLOOR UNITS.
-GRILLES AND REGISTERS.
-( 63) DRYER VENTS WITH WALL BOX AND WALL CAP.
-( 98) DELTA BREEZE BATHROOM EXHAUST FANS.
-( 3) GOODMAN 96% EFFICIENT GAS FURNACES 40k BTU each / 2-ton 13 SEER AC UNITS FOR CORRIDOR’S.
-( 3) FANTECH 150CFM AIR EXCHANGERS (ERV’S) FOR CORIDOOR VENTILATION.
-( 3) GOODMAN 96% EFFICIENT GAS FURNACES / 13 SEER AC UNITS FOR COMMON SPACES.
-SUPPLY AND RETURN DUCTING, GRILLES AND REGISTERS AS NEEDED.
-ELECTRIC SPACE HEATERS FOR STAIRWELL, WATER METER ROOM, AND ENTRY VESTIBLUES.
-GARAGE VENTILATION SYSTEM TO INCLUDE FANS 16,000 CFM , LOUVERS, AND CO/NO2 CONTROLLER.
-SUSPENDED UNIT HEATERS FOR GARAGE HEATING ,250k BTU each x 4.
-NATURAL GAS DISTRIBUTION PIPING AS REQUIRED.
There will be temp gas lines ran up to each floor for temp heat. I’m assuming that there will be 2, 400k heaters on each floor x 4 floors.
There will be 400k BTU temp Heaters in the parking garage x 4.
A temporary 4 million BTU meter will be installed by MDU to supply all temp heaters